文化大學機構典藏 CCUR:Item 987654321/41813
English  |  正體中文  |  简体中文  |  全文笔数/总笔数 : 46962/50828 (92%)
造访人次 : 12457846      在线人数 : 621
RC Version 6.0 © Powered By DSPACE, MIT. Enhanced by NTU Library IR team.
搜寻范围 查询小技巧:
  • 您可在西文检索词汇前后加上"双引号",以获取较精准的检索结果
  • 若欲以作者姓名搜寻,建议至进阶搜寻限定作者字段,可获得较完整数据
  • 进阶搜寻
    主页登入上传说明关于CCUR管理 到手机版


    jsp.display-item.identifier=請使用永久網址來引用或連結此文件: https://irlib.pccu.edu.tw/handle/987654321/41813


    题名: Geometrical parameters analysis of improved circulating inclined fluidized beds for general HVAC duct systems
    作者: Liang, JD (Liang, Jyun-De)
    Hsu, CY (Hsu, Chien-Yeh)
    Hung, TC (Hung, Tai-Chih)
    Chiang, YC (Chiang, Yuan-Ching)
    Chen, SL (Chen, Sih-Li)
    贡献者: 機械工程系暨機械工程學系數位機電研究所
    关键词: AIR-CONDITIONING SYSTEMS
    DESICCANT DEHUMIDIFICATION SYSTEM
    TOTAL HEAT-EXCHANGER
    SILICA-GEL
    SOLID DESICCANT
    PERIODIC-FLOW
    DESORPTION
    VALIDATION
    ADSORPTION
    WHEELS
    日期: 2018-11-15
    上传时间: 2019-01-16 11:29:35 (UTC+8)
    摘要: This study experimentally investigated the influence of geometrical parameters on improved circulating inclined fluidized beds (ICIFB) for HVAC duct systems. The geometrical parameters include the inclined angle, base height of the regeneration bed, and particle channel height of the adsorbent bed. An optimal ICIFB system was developed based on the experimental results. Compared to the circulating erect fluidized bed system (CEFB) and the circulating inclined fluidized bed system (CIFB), the optimal ICIFB system could increase adsorption/desorption performance by 32.4% and 23.5%, respectively, under the same operating conditions. The optimal ICIFB system had the highest energy factor with up to 0.67 kg/kW h, which was 77.9% and 40.1% higher than the CEFB system and the CIFB system, respectively. The total adsorption was also measured for the optimal ICIFB system working nine hours per day (air volume = 850 cm(3)/h) under different monthly outside air conditions in Taiwan. The results showed that year-round total adsorption of 729.5 kg, which was 14.1% more than the CIFB system. The ICIFB system can combine with HVAC duct systems set up above the ceiling. Compared to conventional dehumidification systems, it saves space, has better dehumidification performance, and has a lower pressure drop, thus, it is suitable for residential air-conditioning systems.
    显示于类别:[機械工程系暨機械工程學系數位機電研究所] 期刊論文

    文件中的档案:

    档案 描述 大小格式浏览次数
    index.html0KbHTML168检视/开启


    在CCUR中所有的数据项都受到原著作权保护.


    DSpace Software Copyright © 2002-2004  MIT &  Hewlett-Packard  /   Enhanced by   NTU Library IR team Copyright ©   - 回馈